ANTRACK V1 – Cooling rack for water ASICy
| Specifications | Details |
|---|---|
| Door Design | ANTHRACUS |
| Version | V1 |
| Capacity | 4 ANTMINER units (S19 Hyd./S21 Hyd. series) |
| Maximum load, kW | 24 |
| Detailed characteristics | |
| Size (Length*Width*Height), mm (without packaging) | 1000 * 600 * 2000 |
| Size (Length*Width*Height), mm (with packaging) | 2380 * 1170 * 805 |
| Net weight, kg (without packaging) | 210 |
| Gross weight, kg (with packaging) | 310 |
| Network connection mode | EJ45 Ethernet 10/100M |
| Power supply | |
| Input AC supply voltage, Volt (1-1) | 380 ~ 415 |
| Input frequency range AC, Hz | 50 ~ 60 |
| AC input current, Amp (1-2) | 80 |
| Environmental requirements | |
| Ambient temperature, °C | 15 ~ 45 |
| Water flow, L/min | 32,0 ~ 40,0 |
| Water pressure, bar | ≤3,5 |
| Working fluid (1-3) | Antifreeze (10%) |
| pH of the liquid | 7,0 ~ 9,0 |
| Storage temperature, °C | -20 ~ 70 |
| Operating humidity (non-condensing), RH | 10 ~ 90% |
Note:
- (1-1) Warning: Incorrect input voltage may cause damage to the device.
- (1-2) Three-phase AC input.
- (1-3) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity must be less than 20 μs/cm when the system is first started.
Shipping is not included and will be charged separately. $3,800 USD for DHL priority air shipping and $1,270 for sea shipping, door-to-door. All sales are final. No refunds or cancellations.